Online UPS 15 kVA

Brand: CRYSTAL
Country of Origin – INDIA 

15 kVA | 12 kW | 240 Volt DC System  

Isolation Transformer, IGBT Based
Three Phase input Single Phase Output
Input:    Nominal Voltage: 240/415 vAC
Power Factor: > 0.95    | Frequency: 50/60 Hz
Output: Voltage: 415 Vac

MAX POWER 3 SERIES ON-LINE UPS
– Three Phase Input & One Phase Output
– True on-line double conversion design providing all power protection
– Sine wave pulse width modulation
– IGBT inverter design.
– Wide Input voltage windows
– Pure sine wave output less than 3% THD
– Expandable battery run time
– Generator compatible
– Cold start
– Load/Battery power meter display
– Overload, on-line, battery status LED/LCD
– Advanced Battery Management
– Automatic charging in UPS off mode
– Smart RS-232 communication port (Optional)  
– SNMP Card (Optional)

RATING kVA15 kVA
LOAD POWER FACTOR RANGE0.8 P.F. Lagging
TYPE3 PHASE IN – 1 PHASE OUT
TECHNOLOGYDSP based PWM technology using IGBT
INPUT PARAMETERS 
INPUT SUPPLY3 Phase 4 Wire
VOLTAGE RANGE145V – 270V
FREQUENCY RANGE45-56Hz
OUTPUT PARAMETERS 
POWER12 KW
VOLTAGE REGULATION230 V ± 2% (P-N), 400 V ± 2% (P-P)
FREQUENCY REGULATION50Hz ± 0.1Hz
PEAK EFFICIENCY>92%
OUTPUT WAVEFORMPure Sine Wave
TOTAL HARMONIC DISTORTION<3% at Full Load
LOAD CREST FACTOR03:01
OVERLOAD HANDLING CAPACITY110% for 5 Mins, 150% for 15 Secs, 200% -for 4 Secs, 300% for 2 Secs
BY-PASSRecovery to ± 5% within 1.5 Cycles
BATTERY PARAMETERS 
BATTERY TYPELA/TUBLAR/SMF
BATTERY RECOMMENDATIONFrom 7.2 AH to 200 AH
NO of BATTERY & VOLTAGE20 Nos. 240 Volt DC
BATTERY CHARGING CURRENT3A ± 0.5A to 20A ± 0.5A
BATTERY SELF TESTAutomatic and Manual
ENVIRONMENTAL PARAMETERS 
OPERATING TEMPERATURE0-55° C
ACOUSTIC NOISE (AT 1MTS)<65db
RELATIVE HUMIDITYMax 95% non – condensing
OTHERS 
ALARMMains Failure, Battery Low, Over Load, Short Circute
PROTECTION CLASSIP 20
PROTECTIONShort Circute, Over Voltage & Under Voltage Protection
SHORT CIRCUIT PROTECTION200% LOAD (with in few milliseconds)
MONITORING SOFTWAREAdditional Software available for remote Monitoring
COOLINGForced AIR Cooled
UPS EFFICIENCY>85%

NPR 420,000

Code Online UPS 15 kVA

Brand CRYSTAL

Size 15 kVA 3PH Input 1PH Output 240V DC

Available Yes

Delivery Yes

Call Now